REMARKABLE CHARACTERISTICS
- Extreme purity and quality of the material
- Special Over voltage and Over current resistance, polypropylene dielectric
- Particular slope design of current carrying metal layer vaporized onto one side of the polypropylene film
- Self-healing tecnology
- Progressive method of metal spraying to enlarge the sensitive contact area of winding elements
- Vacuum drying and long high temperature storage to eliminate humidity
- Dry technology-Innovative components of resin filler to keep constant capacitance over an extended period of time. There is no risk of leaking oil or gas
- High and Thin Cylindrical aluminum cases, with special high temperature resistant protective paint can guarantee a natural permanent cooling of the capacitors under heavy working conditions
- Overpressure disconnecting safety device to disconnect the capacitor from the mains at the end of its lifetime or in presence of dangerous overload
- The special design enables capacitors to withstand high switching surge
The “Allpower” Capacitors are designed to be used to improve the Power Factor in tough conditions of the electrical network.
THE “ALLPOWER” ARE SPECIALLY SUITABLE TO WITHSTAND
- Increasing Harmonic distortion on the system up to 25% (due to non linear load with 5-7-8-11-13th degree of harmonic current).
- Recurring Voltage. Voltage interruption and Current boosts due to low quality power networks.
- Fast charging load and a lot of switching operations. The “All power” can be used in different configurations.
- Non-automatic Power Factor correction of individual loads like induction motors, transformers, induction furnace
- Automatic Power Factor correction system for inductive devices and transformers.
- Tuned and Detuned Harmonic filtering Automatic Power Factor correction systems.
INSTALLATION
- Before installing the capacitors it is necessary to check carefully the Current Harmonic distortion in the power system. If non-linear load on you electrical system exceeds 15% of the total load, you can suffer from Harmonic contaminated network.
- Capacitors are suitable for indoor installation, for any mounting position.
- Automatic capacitor banks must be equipped with a cooling fan, activated when the internal temperature exceeds the set value (normally 35 degree C)
- Automatic capacitor banks should be completed with suitable capacitor switching contractors, equipped with pre-making resistors (necessary to protect capacitors from inrush peak currents during switching operation).
- Schedule periodic check and inspections are mandatory to assure capacitors reliable operation.
- Using power factor correction equipment without harmonic filters can cause the harmonics amplification in the network